THE WEAK LINK
Fuses and circuit breakers prevent too much amperage from traveling
through a wire, building heat through resistance that may damage
electrical and electronic equipment, and more important, cause an
electrical fire. You can avoid potentially dangerous problems by
reviewing ABYC standards to make sure adequately sized circuit protection
devices are installed properly.
By Kevin Jeffrey
"Electrical circuit” refers to a complete path for electrical
current flowing through wires. A boat’s power system is comprised
of various electrical circuits formed by connecting a voltage source
such as a battery bank or AC power source to one or more electrical
loads (equipment that uses electricity) by means of a conductor (wire
or cable). In a DC (direct current) circuit, battery voltage pushes
electrical current through various electrical loads when they are
switched on, using some of the energy stored in the battery to perform
useful work. In an AC (alternating current) circuit the voltage source
(shorepower, inverter or gen-set) pushes electrical current in a
similar manner, again using energy in the process.
There are primary or main circuits, which
typically include the main power sources, either DC or AC (Figure
1). There are also secondary or branch circuits that are complete
electrical paths within the primary circuits. All electrical loads
on the boat, for example, are individual secondary circuits. Finally,
there are internal circuits within each electrical or electronic
device.
All electrical circuits must be protected from too
much current flow, which can cause wire conductors to overheat and
wire insulation to burn, and can damage internal circuits in individual
appliances. Protection of an electrical circuit is in the form of
an intentional weak link, typically a fuse or circuit breaker, which
the industry refers to as a overcurrent circuit protection device
(CPD). Circuit protection on board a boat must be taken seriously.
A potentially devastating electrical fire can result when too much
amperage travels through a wire and enough heat is generated to melt
and burn the wire insulation and surrounding materials, causing a
fire.
CPDs are meant to protect against unexpected problems,
and shouldn’t
preclude proper wire sizing and adherence to proper electrical system
design and installation practices. Sizing wire is relatively easy.
You simply match the maximum sustained amperage in a given circuit
and the total length of the circuit wiring with a proper wire size
that will be safe and also prevent an excessive voltage drop for
the type of appliance used (Figure 2). [Ed: For specifics on wire
sizes, factoring in voltage drop, length of run and whether or not
the wire passes through a heated space (i.e. engine compartment),
refer to DIY 1998-#4 issue, or “DC Electrical Systems” CD-ROM,
or sections E-8 and E-9 of ABYC Standards.]
Sizing wire correctly can’t protect against accidental grounding
through wire chafe, equipment failure or grounding a circuit while
performing system maintenance that temporarily allows a dangerous
amount of current to flow. CPDs handle unsafe levels of current by
opening the circuit, either through thermal devices or devices that
sense a magnetic field created by excess amperage.

Figure 1 - Main and Branch Circuit Protection
Types of CPDs

Figure 2 - ABYC Amperage Recommendations

Figure 3 - Quick-Reference Comparison of CPDs
Fuses are strictly thermal devices that melt at a predetermined
amperage. They are reliable and relatively inexpensive, although
total cost includes the purchase of a fuse mounting block and a protective
cover of some type, spares, since fuses must be replaced after each
overcurrent condition, and some form of circuit disconnect. Circuit
breakers can be thermal or magnetic devices, or a combination of
the two. Circuit breakers are typically more expensive than fuses,
especially for high load circuits, but they also serve as circuit
disconnects and since they are resettable the need to carry spares
is not as critical. (Figure 3 illustrates a quick-reference comparison
of CPDs.)
Class T Fuse: Recommended by most inverter manufacturers,
it has an extremely fast short-circuit response, a 20,000 ampere
DC interrupt capacity, and is rated for up to 160 volts DC (VDC).
ANL Fuse: With a 6,000 ampere DC interrupt capacity,
it meets ABYC requirements for main DC circuit protection on large
battery banks with a voltage up to 32DC.
Sea Fuse: An economical choice for circuit protection
between 100 and 300 amperes. It has a 2,000 amperes DC interrupt
capacity and is rated for up to 32VDC.
Automotive Style Fuse: Inexpensive and widely available
through automotive stores, it’s the most economical choice
for between 30- and 80-ampere circuit protection. It has 1,000-ampere
DC interrupt capacity and a 32DC voltage rating.
Glass Fuses: Available in current ratings from less
than 1 up to 50 amperes, these inexpensive fuses are used for branch
circuits in a variety of applications. AGC models are fast-acting
fuses, while MDL models are time-delay fuses for high inrush motor
type loads.
Thermal Circuit Breakers: The T-1 series CPD from
Blue Sea is thermally responsive bi-metal breakers combining switching
and breaker function in one unit. They are available with ampere
ratings from 25 to 150 amperes, a voltage rating of 48VDC, and 5,000
amperes at 24VDC interrupt rating. Blue Sea’s standard thermal
circuit breakers are similar to the T-1 Series but have a 3,000-ampere
DC interrupt rating, a 30VDC voltage rating.
Magnetic Circuit Breakers: Available in a wide range
of styles and ratings, there are standard DC and AC single pole circuit
breakers used for protecting branch circuits in electrical distribution
panels. Some low ampere models, rated as “quick trip” are
designed specifically for electronics. Double pole AC breakers are
available to switch both hot and neutral legs of a 120VAC circuit
or two hot legs of a 240VAC circuit. Standard magnetic circuit breakers
typically have a 2,000- to 3,000-ampere interrupt rating, although
some models are available with a 5,000-ampere interrupt rating.
It used to be that only fuses could handle heavy DC
loads, but high load circuits can now be protected with single, double
or triple pole breakers, such as those from Blue Sea Systems and
Paneltronics. In these devices breakers rated up to 100 amperes each
are ganged to provide various levels of protection. Sizes range from
50-ampere single pole to 300-ampere triple pole models.

Figure 4 - How to Determine Interrupt Rating
Use the table above to determine the required minimum interrupt rating per ABYC, or how much current the fuse or breaker can safely handle in a short circuit condition.
Sizing and Selecting

Figure 5 - Factoring Wire Size
The smallest wire in a circuit determines the amperage of the fuse or circuit breaker.
When choosing CPDs, take it one circuit at a
time. First, choose whether you want a fuse or circuit breaker
for each circuit. Circuits in an explosive vapor area, such as
gasoline engine rooms, battery compartments and propane lockers,
must be protected by a vapor-proof circuit breaker. Then, check
to see what ampere interrupt rating is required for the application
(see Figure 4). Next, make sure the CPD is rated to open at an
amperage greater than the maximum circuit load and less than the
rated amperage capacity of the smallest wire in the circuit. It’s also useful to know the maximum momentary
or surge current experienced in the circuit. Choosing CPDs that can
withstand this surge and still offer the required protection means
you’ll avoid nuisance tripping. As a final check, make sure
the CPD’s voltage rating meets or exceeds the circuit voltage.
Where to Install?


Figure 6 - Sample DC Circuits to ABYC Standards
(top) Single engine and (bottom) twin inboard engine DC electrical systems without AC power systems.
Before locating CPDs in your electrical system,
it’s important
to understand the concept that CPDs are installed to protect individual
wires in a circuit, and that they should be sized specifically for
those wires. Secondary and small branch circuits use smaller (in
number only, larger in size) gauge wires, so smaller CPDs should
be used (Figure 5).
Ultimately every wire on board would be protected,
but that is impractical. In the DC side of an electrical power system,
ABYC standards take a reasonable approach to circuit protection by
exempting mandatory CPDs from wires between batteries, battery switch
and engine starter motor (Figure 6). CPDs are required within 18cm
(7") of the
battery switch and starter motor on wires leading to various loads,
and within 183cm (72") on wires leading to loads directly from
a battery. The 18cm (7") dimension can be extended to 101cm
(40") if wires are enclosed in a sheath or other enclosure in
addition to the wire insulation (Figure 7).
In the AC side, there should be a main circuit breaker
at each AC power source, i.e., at the shorepower inlet(s), generator
output and inverter output (Figure 8). In addition, there should
be branch circuit breakers on every branch circuit. On boats with
multiple sources of AC power, the main circuit breakers can be conveniently
located in an AC source selector panel (Figure 9). This type of panel
allows only one AC power source to be capable of supplying power
at any given time. In this case the main circuit breakers also are
serving as manual circuit disconnect switches.

Figure 7 - The 7-40-72 Rule.

Figure 9 - Sample AC Selector panel.




Figure 8 - Sample AC Circuits to ABYC Standards
(1) Single-phase 120V shorepower with shore-grounded
(white) neutral conductor and grounding (green) conductor. (2)
A 120VAC generator included as an additional AC power source. In
both diagrams the ungrounded conductor and the grounded neutral
are protected with a single overcurrent protection device that
simultaneously opens both current-carrying conductors. ABYC does
not recommend fuses to serve this function. 120VAC branch circuits
are permitted to be single pole in the ungrounded current carrying
conductors. (3) Single-phase 120/240VAC system with shore-grounded
(white) neutral conductor and grounding (green) conductor. Each
ungrounded shore conductor connects through the shorepower inlet
to the boat’s AC electrical system through a single overcurrent
protection device that simultaneously opens both ungrounded conductors.
The shore-grounded neutral connects to the boat’s AC electrical
system without overcurrent protection. It may be used provided
the overcurrent protection device opens all current carrying conductors
in the circuits (in this case a 3-pole switch is needed). (4) An
isolation transformer system with single phase, 240VAC shorepower
input and 120/240VAC output from the transformer. Circuit protection
is provided by a main shorepower disconnect on the shore side of
the transformer and secondary overcurrent protection on the boat
system side of the transformer. Each ungrounded shore current carrying
conductor connects from the shorepower inlet to the primary winding
of the isolation transformer through an overcurrent protection
device that simultaneously opens both ungrounded conductors. 120VAC
branch circuit breakers are permitted to be single pole in the
ungrounded current carrying conductors. 240VAC branch circuit breakers
must be two-pole and simultaneously open all current carrying conductors.
About the author: Kevin Jeffrey works as an
independent electrical power consultant and is the author of
the “Independent Energy
Guide” and publisher of “Sailor’s Multihull Guide” available
soon in its third edition.
Resources
“Standards and Technical Information Reports for Small Craft,” American
Boat & Yacht Council; Tel: 410/956-1050, Website: www.abycinc.org
Ratings Stats
CPDs have ratings that help describe their intended purpose and how
they function, as well as help customers make good decisions where
and when to use them.
Amperage Rating: The amperage used to calculate the
opening speed of the device, not the actual amperage at which the
CPD will trip or “blow.” It usually takes an additional
20% or so of amperage above the rated value for the CPD to trip.
Opening Speed or Delay: The relationship between the
percentage a CPD is operating over its amperage rating and the length
of time required for it to open. The higher the percent of current
flow to amperage rating, the faster the circuit protector opens.
Interrupt Rating: How much current the fuse can safely
handle in short circuit situations. Refer to Figure 4 on page 13
to determine what minimum interrupt rating is required.
Voltage Rating: The maximum voltage for the circuit
in which the fuse is used. |